OPGW with PBT Tube


Material:  


Product Features

Specifications

Technical Specifications

  YamNoYamNoMaterial Dia.
 FiberG.652Dto 96 CoresSM or MM0   
 CenterAL-Tube1  Tube-Dia.6.2/9.7mm
StructureLayer 120.3% AS wire740% AS wire4Diameter3.70mm
         
         
         
         
 According to IEC, IEEE, DL/T 832-2003, GB/T 7424.4-2003 standards  
 Stranding direction of outer layer is right hand(Z-stranding)   
 Cable Diameter    17.1mm
 Cable Weight    850kg/km
 Supporting Cross Section    162.0mm2
  Section of AS Wire118.27mm 2   
  Section of AA Wire0.00mm 2   
  Section of AL tube43.71mm 2   
 Rate Tensile Strength (RTS)   120.0kN
Technical DataModulus of Elasticity (E-Modulus)   119.3kN/ mm2
 Thermal Elongation Coefficient   14.9×10 -6 /℃
 Permissible Maximum Working Stress (40% RTS)  296.4N/ mm2
 Everyday Stress(EDS) (16%~25% RTS) 118.6~185.2N/ mm2
 Ultimate Exceptional Stress (70% RTS)  627.9N/ mm2
 DC Resistance    0.294Ω/km
 Short Time Current (0.3s, 20℃~200℃)  25.1kA
 Short Time Current Capacity I 2 t   188.3kA 2 s
 Minimum Bending Radius:Installation:  342mm
   Operating:  256mm
TemperatureInstallation    -10℃ ~ +50
Range:Transportation and Operation   -40℃ ~ +80

All Sizes and values are nominal
Diameters Tolerance: +/-2% / Weight Tolerance: +/-2%

 

Types of fibers available

    • Singlemode: G652D
    • G655 singlemode ,  NZDS (Non Zero Dispersion Shifted) fibers
    • Multimode OM2
    • Multimode OM3

Applications

  • Aerial facilities
  • High voltage distribution lines
  • Medium voltage distribution lines

Quality

There are different series of tests to ensure the quality of OPGW:

  • Routine testing  (testing in progress according to the internal quality plan)
  • Factory Acceptance Test  (FAT, witnessed by the customer)
  • Type testing  (only in case of a new basic design, repetition in exceptional cases)

OPGW testing must be in accordance with applicable standards or agreements between the purchaser and the manufacturer. As a general rule, testing will be performed in accordance with IEC 60794-4-10. However, if necessary, testing can be performed in accordance with IEEE Std 1138.

Type testing  may be waived upon presentation of the manufacturer's certificate for the similar product, which has been carried out by an independent testing organization or internationally recognized laboratory. If type testing must be carried out, it shall be carried out in accordance with an additional type testing procedure agreed upon between the purchaser and the manufacturer.

Routine Testing The optical attenuation coefficient for all production cable lengths is measured according to IEC 60793-1-CIC (backscattering technique, OTDR). Standard single-mode fibers are measured at 1310nm and 1550nm. Non-zero dispersion single-mode (NZDS) fibers are measured at 1550nm.

Factory  acceptance testing is carried out on two samples per order in the presence of the customer or their representative. The requirements for quality characteristics are determined by the relevant standards and agreed quality plans.

Installing OPGW requires some additional planning, as it's impractical to splice an OPGW cable mid-span; purchased cable lengths must be coordinated with the spans between towers to avoid waste. When fibers must be joined between lengths, a weatherproof splice box is installed on a tower; a similar box is used to transition from the OPGW to a single-fiber cable plant to connect the fibers to terminal equipment.